Psw1, Psw2, Ovrd – KMC Controls BAC-8007 Installation Guide User Manual
Page 38

Procedure
Steps
STE display
3
Change Password 1.
Note:
Entering four zeros (0000) removes the
password.
1.
Press the
or
buttons to change the first
digit.
2.
Press the
Set
Point
button to select the next digit.
Repeat for all four digits.
3.
When the
Set
Point
button is pressed for the last
digit, the new password is saved and the
display advances.
PSW1
OOOO
4
Change Password 2.
Note:
Entering four zeros (0000) removes the
password.
1.
Press the
or
buttons to change the first
digit.
2.
Press the
Set
Point
button to select the next digit.
Repeat for all four digits.
3.
When the
Set
Point
button is pressed for the last
digit, the new password is saved and the
display advances.
PSW2
OOOO
5
Set the local unoccupied
override timer.
Applies only to STE-6017
sensors.
1.
Press the
or
buttons to set the local
unoccupied override timer. The value will
change in 1 minute increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
3O
OVRD
6
Set the standby time
Applies only to STE-8201
sensors.
1.
Press the
or
buttons to set the time for
the standby time. The value will change in 1
minute increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
15
7
Set discharge air
temperature limiting.
Not used for all models.
Required for reheat.
1.
Press the
or
buttons to enable or disable
discharge air temperature limiting.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
DISABLE
DAT
Procedure to set the advanced options (continued)
Section 4: Configuring the controllers
SimplyVAV
38
Revision E