KMC Controls CTE–1103 User Manual

Installation guide, Dual temperature room thermostat, Mounting

background image

Installation Guide

Dual Temperature Room Thermostat

CTE –1003, 1004, 1103

Mounting

Standard:

The base unit’s mounting slots are designed to align with the
holes in a standard 2" x 4" (51x102) handy conduit box.

Use a 2" (51) deep box if using conduit.

Normal screw and anchor systems may be used on solid
walls.

Hollow wall:

1. Cut a 3-3/4" x 1-3/4" rectangular opening in the wall.

(Check if unit is horizontal or vertical before cutting)

2. Make all necessary connections

3. Insert Toggle Bolt Assembly (HMO-5001, ordered separately)

through the wall and tighten.

Care should be taken not to bend or flex the base of the
thermostat.

Required Tools

• digital voltmeter
• small phillips screwdriver
• small flatblade screwdriver

• keyhole saw

Wiring

Typically, T1 and T3 are used for cooling and T2 and
T4 are used for heating. Refer to the wiring
diagram.

CTE–1004 has a jumper installed from terminal
“A” to terminal “4”.
This causes the thermostat to
switch to an auxiliary flow lever when a call for
heating begins. This flow level may be adjusted
under the cover . If auxiliary flow is not needed,
remove the jumper.