The averaging temperature sensor incorporates sev-

eral discrete sensors encapsulated at equal distances

across the length of the probe. The complete as-

sembly acts as a single sensor to monitor the average

temperature in a duct. Averaging elements are not

recommended for high humidity applications.

Mounting 1
Connections and Wiring 2
Configuration 2
Maintenance 2
Specifications 2
More Information 2
Important Notices 2

Use

Tie Wraps

to Secure

Cable

2"

Min.

Bend

Radius

115.8 mm

4.56"

Foam Gasket

53.6 mm

2.110"

84.3 mm

3.320"

Mounting Holes (X2) Ø 0.200"

Various Cable Lengths

2X Ø 0.850”

FT6 Plenum rated cable

The sensors can be installed onto hangers in the

duct using tube clamps or wire ties. They should

be located in a straight section of duct away from

heating, cooling, or humidifier elements.
Temperature sensors can be affected by air stratifica-

tion in the duct, air leakage through the conduit

or other duct holes, and nearness to exterior walls,

a large thermal mass (e.g., concrete blocks), heat

sources, or wires with power.
Because of air stratification, the coldest air tends to

be toward the bottom of the duct. Hence, one of the

sensors should be near the bottom of the duct.
The flexible cable can be easily shaped to fit any duct

size but observe a minimum bend radius of two

inches to prevent damage to wires or sensors.
1. Cut a hole in the duct large enough to feed the

sensor cable through the back of the sensor

enclosure.

2. Fasten the enclosure to the duct by drilling holes

in the duct and threading screws through the

mounting holes in the case.

3. Insert the sensor cable into the duct, stringing the

cable to cover the air path, and secure as needed.

4. For the cable leading to the building automation

system controller, attach conduit to a hole in one

of the sides.