Modulating reheat

This application is for a BAC-8005 or BAC-8205 controller. The modulating
option for reheat can control either an electric reheat unit with an analog
input or a modulating hot water valve. The analog reheat output at output
terminal AO3 varies between 0 and 10 volts DC.

For cooling and heating, a duct temperature sensor is required for Discharge
Air Temperature limiting and automatic changeover. See the topic

Advanced

options

on page 37

for instructions to enable Discharge Air Temperature

limiting.

When connecting the controller to a fan powered VAV unit, the fan circuits
must be compatible with the following specifications.

The fan start circuit is a 24 volt AC pilot duty output.

The fan speed output is 0-10 volts DC.

Submittal sheets for several variations of this application are available from
the

Resources

page at

www.SimplyVAV.com

.

Illustration 6–3 Modulating reheat

ON CTS

1 2

COMM
READY

AI1

AI5

GND

AO4

AO3

SC

BO8

BO5

BO6

SC

BO7

24VAC

AI6

GND

AI7

T

-S
T

A

T

/

SEN

SO

R

-A

+B

S

EO

L

BACnet MS/TP

Fan
Speed
0-10 VDC

Duct

Temp

Sensor

Analog

Heat

24VAC
Fan start

24 VAC

Class 2

Section 6: Application drawings

SimplyVAV

52

Revision E