loop is at 50%, the reheat output is

On

for 5 seconds and

Off

for 5 seconds. If

the Reheat loop is less than 10%, the reheat output remains at zero.

See the topic

Time proportional reheat

on page 53

for an application drawing.

Illustration 7–5 Time proportional reheat operation

Room temp increase

HTG SP

-2F

HTG SPAN

lo

o

p

%

0

100

10

HTG %

R

e

h

e

a

t

Floating reheat

If the controller is configured for floating reheat, it controls two binary triac
outputs to drive the inputs of a tri-state actuator connected to a valve. If the
Reheat loop is less than 30%, the valve is driven closed. If the loop is greater
than 70%, the valve is driven open. If the loop is in between 30% and 70%, no
valve action is taken.

See the topic

Floating reheat

on page 54

for an application drawing.

Illustration 7–6 Floating reheat operation

HTG %

DRIVE

OPEN

DRIVE

CLOSED

lo

o

p

%

0

100

70

R

e

h

e

a

t

30

HTG SP

HTG SPAN

-2F

Room temp increase

NO ACTION

Section 7: Sequences of operation

SimplyVAV

68

Revision E