KMC Controls BAC-8007 Installation Guide User Manual
Page 63

Illustration 7–1 DAT limiting operation
HTG SP
HTG SPAN
50%
100%
0%
ROOM TMP
DAT loop
ROOM TMP+
15°
(Max 90°F)
If DAT Limiting is enabled, and a DAT sensor is not connected, the controller
will lockout reheat control only in the cooling mode. The unit will operate
this way until a DAT sensor is detected or until the unit is commanded to
control to the Active Heating Setpoint by a supervisory BMS.
If the unit has detected a DAT sensor and DAT Limiting is not enabled, the
unit’s reheat is controlled by the Heating loop instead of the DAT loop.
See also the topics
and
.
SimplyVAV
Section 7: Sequences of operation
Revision E
63