Illustration 7–1 DAT limiting operation

HTG SP

HTG SPAN

50%

100%

0%

ROOM TMP

DAT loop

ROOM TMP+

15°

(Max 90°F)

If DAT Limiting is enabled, and a DAT sensor is not connected, the controller
will lockout reheat control only in the cooling mode. The unit will operate
this way until a DAT sensor is detected or until the unit is commanded to
control to the Active Heating Setpoint by a supervisory BMS.

If the unit has detected a DAT sensor and DAT Limiting is not enabled, the
unit’s reheat is controlled by the Heating loop instead of the DAT loop.

See also the topics

Changeover

on page 62

and

Input sources

on page 58

.

SimplyVAV

Section 7: Sequences of operation

Revision E

63