Procedure

Detailed steps

STE display

7

Set the heating maximum
airflow limit.

1.

Press the

or

buttons to set the maximum

limit for heating airflow. The setpoint will
change in 1 CFM increments.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

3SO

MXHT

8

Set the minimum limit
for fan speed.

Not used for all models.

1.

Press the

or

buttons to set the minimum

limit for the fan speed. The setpoint will
change in 1% increments.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

/

-).&

9

Set the maximum limit
for fan speed.

Not used for all models.

1.

Press the

or

buttons to set the maximum

limit for the fan speed. The setpoint will
change in 1% increments.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

//

-!8&

10

Set the dual duct
minimum airflow.

Not used for all models.

This setpoint is for the minimum airflow when a
dual-duct system is at temperature setpoint.

1.

Press the

or

buttons.

2.

Press the

Set

Point

button to save the setpoint and

advance to the next function.

//

$,-.

11

Select a new
configuration function or
exit.

1.

Press the

or

buttons to select one of the

following:

STPT

,

BOX

,

ADVC

, or

RSTR

options

BACK

to choose another configuration

function

EXIT

.

2.

Press the

Set

Point

button to select the next function.

FLOW

Procedure to set the airflow setpoints (continued)

Section 4: Configuring the controllers

SimplyVAV

36

Revision E