Procedure
Detailed steps
STE display
7
Set the heating maximum
airflow limit.
1.
Press the
or
buttons to set the maximum
limit for heating airflow. The setpoint will
change in 1 CFM increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
3SO
MXHT
8
Set the minimum limit
for fan speed.
Not used for all models.
1.
Press the
or
buttons to set the minimum
limit for the fan speed. The setpoint will
change in 1% increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
/
-).&
9
Set the maximum limit
for fan speed.
Not used for all models.
1.
Press the
or
buttons to set the maximum
limit for the fan speed. The setpoint will
change in 1% increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
//
-!8&
10
Set the dual duct
minimum airflow.
Not used for all models.
This setpoint is for the minimum airflow when a
dual-duct system is at temperature setpoint.
1.
Press the
or
buttons.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
//
$,-.
11
Select a new
configuration function or
exit.
1.
Press the
or
buttons to select one of the
following:
STPT
,
BOX
,
ADVC
, or
RSTR
options
BACK
to choose another configuration
function
EXIT
.
2.
Press the
Set
Point
button to select the next function.
FLOW
Procedure to set the airflow setpoints (continued)
Section 4: Configuring the controllers
SimplyVAV
36