KMC Controls SSE-2000 Series User Manual
Installation guide, Mounting, Connections and wiring
SSE-1000/2000 Series
1
Installation Guide
Installation Guide
VAV System Duct Flow Sensors
SSE-1000/2000 Series
Mounting
The SSE-1000 and SSE-2000 sensors are designed to
mount to the VAV box’s inlet collar. The sensor head’s
foam backing prevents conditioned air leakage.
1. Cut a 7/8" hole in the duct.
2. Insert the sensor.
3. Align the sensor horizontally to maintain
calibration at zero airflow.
4. Fasten with two 3/16" sheet metal screws.
5. Add a 2" x 4" standoff type conduit box if wiring
must be run through conduit.
Connections and Wiring
See the diagrams below. See also the CEP-4000 illustra-
tion on the next page.
• Sensor
terminals 1, 2, and 3 connect to CEP-4000
terminals 1, 2, and 3 respectively.
•
SSE-2000 series terminals “X” and “Y” connect to
a heat/cool relay module.
CAUTION
To prevent damage to the SSE series sensors, do not
touch or handle the interior wire windings.
24
VAC
REE1005 Relay Module
CEP4000 Series
Controller-Actuator
7
6
5
4
3
2
1
8
9
10
11
12
13
14
T1
+
T2
R2
R1
T3
CTE1103 Thermostat
X
Y
NC
5
4
T4
C
NO
A
SSE2001/2002
Flow Sensor
1
2
3
Y
X
Sample Application
(Cooling/Heating Changeover)
Connections and Wiring 1
Adjustments and Calibration 2