Occl – KMC Controls BAC-8007 Installation Guide User Manual
Page 28

Procedure
Detailed steps
STE display
3
Set the minimum cooling
setpoint.
This setpoint limits the lowest temperature that a
user can enter as the active setpoint.
1.
Press the
or
buttons to set the minimum
cooling setpoint. The setpoint will change in
0.5° increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
MIN
68O
4
Set the maximum heating
setpoint.
This setpoint limits the highest temperature a
user can enter as the active setpoint.
1.
Press the
or
buttons to set the maximum
heating setpoint. The setpoint will change in
0.5° increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
MAX
78O
5
Set the occupied cooling
setpoint.
This setpoint is used as the active setpoint when
the space is occupied.
1.
Press the
or
buttons to set the occupied
cooling setpoint. The setpoint will change in
0.5° increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
Note:
This setpoint can also be changed as
described in the topic
.
OCCL
74O
Procedure to set the temperature setpoints (continued)
Section 4: Configuring the controllers
SimplyVAV
28
Revision E