beautypg.com

KMC Controls TPE-1483 Series(2004-2008) User Manual

Tpe–1483 series, Pressure transducer, Description

background image

Description

The KMC TPE–1483 series of pressure transducers
incorporates a Wet / Wet differential pressure
transmitter featuring low hysteresis, excellent
repeatability, and long-term stability.

Up to four field-selectable input ranges are available
in most models. The field selectable feature
provides a single model that can be configured to
cover all the input pressure ranges for any given
application.

Three output ranges are field selectable, 4 to 20mA,
0 to 5 VDC, and 0 to 10 VDC. The output signal is
factory calibrated and temperature compensated
for the highest start-up accuracy.

The TPE–1483 can be powered from either a 24
VAC nominal or 12 to 30 VDC power source.
TPE–1483 incorporates a rugged NEMA 4
enclosure.

TPE–1483 Series

Pressure Transducer

Specifications and design subject to change without notice.

Models

The following models are available

TPE–1483–1

0 to 5/10/25/50 psig/d

TPE–1483–2

0 to 10/20/50/100 psig/d

TPE–1483–3

0 to 50/100/250/500 psig/d

Features

Push-button and remote zeroing terminal

Uni-directional or bi-directional pressure range

selection switch

High / low port swap switch to solve incorrect
plumbing for differential

Normal or slow surge damping switch to
prevent false alarms and reduce noise

Output polarity reverse switch

Application

KMC TPE–1483 Pressure Transducers are suited for
any application requiring a reliable pressure
monitor providing a dependable conditioned and
compensated signal output.

The TPE–1483 may be used with any liquid or gas
that is compatible with 17–4 PH stainless steel.

DO NOT USE for these applications:

Oxygen service

Explosive/hazardous environments

Flammable or combustible materials

Valid late 2004 into 2008—
see Rev. C of this data
sheet for information on the
new case and board.