KMC Controls TPE-1483 Series(2004-2008) User Manual
Tpe–1483 series, Pressure transducer, Description
Description
The KMC TPE–1483 series of pressure transducers
incorporates a Wet / Wet differential pressure
transmitter featuring low hysteresis, excellent
repeatability, and long-term stability.
Up to four field-selectable input ranges are available
in most models. The field selectable feature
provides a single model that can be configured to
cover all the input pressure ranges for any given
application.
Three output ranges are field selectable, 4 to 20mA,
0 to 5 VDC, and 0 to 10 VDC. The output signal is
factory calibrated and temperature compensated
for the highest start-up accuracy.
The TPE–1483 can be powered from either a 24
VAC nominal or 12 to 30 VDC power source.
TPE–1483 incorporates a rugged NEMA 4
enclosure.
TPE–1483 Series
Pressure Transducer
Specifications and design subject to change without notice.
Models
The following models are available
TPE–1483–1
0 to 5/10/25/50 psig/d
TPE–1483–2
0 to 10/20/50/100 psig/d
TPE–1483–3
0 to 50/100/250/500 psig/d
Features
◆
Push-button and remote zeroing terminal
◆
Uni-directional or bi-directional pressure range
selection switch
◆
High / low port swap switch to solve incorrect
plumbing for differential
◆
Normal or slow surge damping switch to
prevent false alarms and reduce noise
◆
Output polarity reverse switch
Application
KMC TPE–1483 Pressure Transducers are suited for
any application requiring a reliable pressure
monitor providing a dependable conditioned and
compensated signal output.
The TPE–1483 may be used with any liquid or gas
that is compatible with 17–4 PH stainless steel.
DO NOT USE for these applications:
◆
Oxygen service
◆
Explosive/hazardous environments
◆
Flammable or combustible materials
Valid late 2004 into 2008—
see Rev. C of this data
sheet for information on the
new case and board.