TPE-1464 Series Gauge Pressure Transducers

1

Installation Guide

Installation Guide

Gauge Pressure Transducers

TPE-1464 Series

Mounting 1
Plumbing 1
Wiring 2
Set-Up 3

Configuration 3
Jumper Settings

3

Range 3
Slow Damping

3

Output Reverse

3

Operation 3
Calibration 3

Maintenance 3

Mounting

Avoid locations with severe vibrations or excessive

moisture. The enclosure has a standard 1/2" conduit

opening and may be installed with either a conduit

coupler or a cable gland type fitting.
1. Mount on a vertical surface with the pressure

ports on the bottom.

2. Use screws in the tab holes to fasten the assembly

to the mounting surface.

3. Ensure there is enough space around the unit to

make the pressure and electrical connections.

Plumbing

1. Use appropriately rated pressure tubing for the

1/8" NPT female connection.

2. Arrange the tubing to minimize stress on the

connections.

NOTE: This document is for units available start-

ing in late 2008. See the original installation

guide available on the KMC web site for in-

stallation and configuration information on

older units with a different case and board.

CAUTION

Ensure that the maximum individual port
pressure does not exceed the maximum
pressure range of the unit.

WARNING

Do not use:
• In an explosive or hazardous environment.
• With combustible or flammable gasses.
• As a safety or emergency stop device.
• In any other application where failure of the

product could result in personal injury.

CAUTION

Do not allow debris to get into the pressure
ports since contamination can damage the
sensor.

CAUTION

Use electrostatic discharge precautions during
installation.

114.3 mm

4.5"

64 mm

2.5"

100 mm

3.95"

Ø 0.850”

Mounting Holes

(X4) Ø 0.200”

88.9 mm

3.5"

145 mm

5.7"

1/8” NPT Female

34.93 mm

1.375"

19 mm

0.75"

25.4 mm

1"