Damper operation

Damper movement is determined by comparing the actual airflow reading to
the airflow setpoints. If the actual airflow is within 5% of the setpoint, no
damper action is initiated. Once within the 5% deadband, the actual airflow
must be outside a 7% deadband before damper position changes.

Fan operation

The SimplyVAV controllers support both series and parallel fan powered
VAV units. For either type of fan operation, the fan is controlled through the
following terminals.

A binary output triac controls a 24-volt fan starting circuit. See the topic

Configuring the VAV Box options

on page 31

for the procedure to

configure the controller for a fan.

A 0-10 volt DC analog output controls the speed of the fan. The output
controls fan speed at either Min Fan Speed or Max Fan Speed. See the
topic

Set the airflow setpoints

on page 34

for the procedure to set the fan

speeds.

If the VAV unit is not configured for a fan, the two outputs are not used and
remain inactive regardless of the occupancy state.

Series Fan

If the controller is configured for a series fan, any time the Occupancy mode
of the controller is set to either

Occupied

or

Standby

, the fan runs

continuously. The fan speed is set to Maximum Fan Speed when the state is

Occupied

and set to Minimum Fan Speed when the state is

Standby

.

When the Occupancy state is

Unoccupied

, the fan starts and runs at minimum

speed only on a call for heating. The fan starts when the Heating loop is
greater than 5% and stops when the Heating loop is less than 1%.

Illustration 7–2 Series fan operation

UNOCCUPIED/

STANDBY

STANDBY

MAX FAN SPEED

MIN FAN SPEED

FAN OFF

OCCUPIED

HTG SP

ROOM TEMP INCREASE

SimplyVAV

Section 7: Sequences of operation

Revision E

65