beautypg.com

Parallel fan, Reheat sequence, Modulating reheat – KMC Controls BAC-8007 Installation Guide User Manual

Page 66

background image

Parallel Fan

If the controller is configured for a parallel fan, any time the Occupancy mode
of the controller is set to either

Occupied

or

Standby

and there is a call for

heat, the fan runs continuously. The fan starts when the Heating loop is
greater than 5% and stops when the Heating loop is less than 1%.

When the unit Occupancy state is

Unoccupied

, the fan starts and runs at

minimum speed only on a call for heating. The fan starts when the Heating
loop is greater than 5% and stops when the Heating loop is less than 1%.

Illustration 7–3 Parallel fan operation

MAX FAN SPEED

MIN FAN SPEED

FAN OFF

OCCUPIED

HTG SP

ROOM TEMP INCREASE

UNOCCUPIED/

STANDBY

Reheat sequence

The SimplyVAV controllers can control four types of reheat installations.

Modulating reheat

Staged reheat

Time proportioned reheat

Floating reheat

All reheat is controlled by either the Heating loop or the Discharge Air Temp
Limiting (DAT) PID loop. Loops are described in the topic

PID control loops

on page 61

.

If Discharge Air Temp Limiting is enabled, reheat is controlled by the
DAT PID loop.

If DAT control is not enabled, reheat is controlled by the Heating loop.

In the following descriptions, the loop controlling reheat is referred to as the
Reheat loop.

Modulating reheat

If the controller is configured for modulating reheat, it controls an analog
reheat unit with 0-10 volts DC at the analog reheat output. On a call for

Section 7: Sequences of operation

SimplyVAV

66

Revision E

This manual is related to the following products: