Entering system temperature setpoints and limits, Cnfg stpt – KMC Controls BAC-8007 Installation Guide User Manual
Page 27
![background image](/manuals/637630/27/background.png)
Entering system
temperature
setpoints and limits
The system temperature setpoints set the operational parameters and limits
for the VAV terminal unit.
The temperature setpoints include the following items.
Minimum cooling and maximum heating setpoints
Occupied and unoccupied cooling setpoints
Occupied and unoccupied heating setpoints
Changeover differential setpoint
Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is
described in detail in the topic
Getting started with configuration
Tip:
Once the following procedure is started, all steps must be completed in
order.
Procedure
Detailed steps
STE display
1
Start at the temperature
display.
1.
Start at the temperature display.
2.
Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is
correct.
3
237
////
2
Select the setpoint
display.
1.
From the
CNFG
display, press the
or
buttons to show
STPT
.
2.
Press the
Set
Point
button to select the
CNFG
options.
The display changes to
STPT
.
3.
Press the
Set
Point
button to select
STPT
. The display
changes to
MIN
.
CNFG
STPT
Procedure to set the temperature setpoints
SimplyVAV
Section 4: Configuring the controllers
Revision E