CCC-1001/1002 (Dual Input Receiver Controllers)

1

Installation Guide

Connections

Mounting

Installation Guide

Dual Input Receiver Controllers

CCC-1001/1002

The CCC-1001 and CCC-1002 are not position sensi-

tive, but they must be calibrated and mounted in the

same orientation.
1. Locate the three mounting ears (flanges) on the

unit.

2. Place the controller on the mounting surface and

mark the locations of the two top ears.

3. Partially install two mounting screws (#8 or #10)

on the marks. These should be 3-1/2" (89 mm)

apart.

4. Slide the top ears under the screws.
5. Install the third mounting screw in the bottom ear

and tighten all three screws.

The units are supplied as Direct Acting (DA). If

Reverse Acting (RA) is required:
1. Locate the tubing connections on the back of the

controller.

2. Cut the branch tubing at the DA connection

(lower right corner).

3. Remove tubing from the two-prong guides.
4. Connect branch tubing to the RA connection

(upper right corner) using brass fittings

(provided).

5. Secure extra tubing in the two-prong guides.

A CCC-1001/1002 controller has five 3/16" (5 mm)

ports to accept 1/4" (6 mm) O.D. polyethylene tubing.

Connect the controller to other units as follows:
1. Main control air to Port M. This should be 20 psig

(137 kPa), 30 psig (207 kPa) max.

2. Primary input, 3–15 psig, to Port 1.
3. Remote setpoint adjustment, 3–15 psig with a +/–

10% offset, to Port 2.

4. Secondary input to Port 3.

CCC-1001 Shown

M

M

M

M

Primary Transmitter

(sensed medium, e.g., hot water)

Restrictor

Restrictor

Optional Secondary Transmitter

(sensed medium, e.g., outside air)

Optional Remote

Setpoint Adjust

Regulator

Controlled

Device

Primary Input:

1

Output Signal:

B

Main Air:

MAIN

Secondary Input:

3

Remote Setpoint:

2

CAUTION

Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.

Mounting

1

Connections

1

Adjustments and Calibration 2

CCC-1001 Controller

2

CCC-1002 Controller

2

Throttling Range Adjustment 2
Authority Calibration

2

Setpoint Calibration 3
Remote Setpoint Adjustment 3

Accessories

3

Maintenance

3

Competitor Cross-Reference 4

CCC-1001 =

2-3/16" (56 mm);

CCC-1002 =

2-5/16" (59 mm)

This manual is related to the following products: