BAC-12xx36/13xx36/14xx36 Series FlexStat

1

Installation Guide, Rev. C

Installation Guide (3/6 Outputs)

BAC-12xx36/13xx36/14xx36 Series FlexStat

3 Relays, 6 Analog Outputs, 6 External Inputs

Quick Start

1

Mounting

1

Connections and Wiring 2

Wiring Considerations 2
Network Wiring

2

MS/TP EOL (End-Of-Line) Termination

2

Input Connections 3
Output Connections 3
Power Connection 4

Configuration 4
Applications Notes and Cautions 4
Maintenance

4

Applications

5

FCU (Fan Coil Unit)—2 Pipe, Modulating 5
FCU—4 Pipe, Modulating

6

AHU (Air Handler Unit)—1 Heat and 1 Cool

7

AHU—1 or 2 Heat and Modulating Cool

8

AHU—Modulating Heat and 1 or 2 Cool

9

AHU—Modulating Heat and Modulating Cool

10

AHU—Additional Options

11

Important Notices 11
Additional Resources

11

Mounting

Quick Start

CAUTION

This document is for 3-relay, 6-analog-output,
6-external-input BAC-12xx36/13xx36/14xx36 series
only.

THESE MODELS ARE NOT COMPATIBLE

WITH THE BACKPLATES OF OLDER BAC-10000
SERIES FLEXSTATS (WITH ONLY 3 EXTERNAL
INPUTS)!

If replacing an older 3-input FlexStat,

replace the backplate as well. See other installation
guides for other models.

To select and use a FlexStat in an application:
1. Select the appropriate model for the intended

application and options (see the FlexStat Data

Sheet).

2. Mount and wire the unit (see this Installation

Guide).

3. Configure/program the unit (see the FlexStat

Operation and Application Guides).

4. If necessary, troubleshoot any issues (see the

FlexStat Operation Guide).

5. Operate the unit (see the FlexStat Operation

Guide).

NOTE: This document gives basic mounting,

wiring, and setup information only. For

configuration, programming, operation,

and other information, see the KMC

Controls web site for the latest documents.

Illustration 1—Dimensions and Installation

C

A

B

EIA-485 data

port (for quick

network access)

Terminal blocks on

backplate (rotated on

BAC-13xxxx/14xxxx)

Models

Dimensions in Inches (mm)

A

B

C

BAC-12xxxx (shown) 1.125 (29)

5.551

(141)

4.192 (106)

BAC-13xxxx/14xxxx 1.437 (36.5)

5.192 (132)

For optimum temperature sensor performance,

the FlexStat must be mounted on an interior wall

and away from heat sources, sunlight, windows,

air vents, and air circulation obstructions (e.g.,

curtains, furniture). Additionally, for a model with

an occupancy sensor option, install it where it will

have unobstructed view of the most typical traffic

area. (See the FlexStat Application Guide for more

information.)
If replacing an existing thermostat, label wires as

needed for reference when removing the existing

thermostat.
1. Complete rough-in wiring at each location prior

to thermostat installation. Cable insulation must

meet local building codes.

CAUTION

To prevent mounting screw heads from touching the
circuit board in the thermostat, use only the mounting
screws supplied by KMC Controls. Using other screws
may damage the FlexStat. Do not turn screws in
farther than necessary to remove the cover.

2. If the cover is locked on the backplate, turn the

hex screws in the bottom and top of the FlexStat

CLOCKWISE until they (just) clear the cover.

(See Illustration 1.) Pull the cover away from the

backplate (mounting base).

3. Route the wiring through the backplate.
4. With the embossed “UP” and arrows toward the

ceiling, fasten the backplate to a wall handy-box.

BAC-12xxxx models mount directly on vertical 2

x 4 inch boxes, but they require an HMO-10000/

HMO-10000W wall mounting plate for horizontal

or 4 x 4 boxes. BAC-13xxxx/14xxxx models mount

directly on any of those types of boxes.

5. Make the appropriate connections to the terminal

blocks. (See the Connections and Wiring section.)

6. Place the FlexStat cover over the backplate while

being careful not to pinch or dislodge any

wiring. Back the hex screws (counterclockwise)

out of the brackets until they engage the FlexStat

cover and hold it in place.

Cover locking hex screws

Embossed “UP” indicator