Publication 1404-UM001F-EN-P - November 2009

Chapter 4 Communication

TIP

Some legacy power monitor units with optional DeviceNet
communication do no support remotely settable node addressing,
AutoBaud, or Program Baud. You can check whether your power
monitor supports these functions by viewing the Optional
Communication Card status by using your display module.
Communication type 81 does not support these functions, type 88
does. You may also view this status item by a read of assembly
instance 23, element 25.

Optional DeviceNet Communication Configuration Summary

Parameter Description

Range

Default

User
Setting

Node
Address

DeviceNet node
number (MAC ID)

0…64 decimal

63

Baud Rate

DeviceNet
Communication
Rate

0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
4 = Program Baud

0 = 125 Kbps

Bus-off
Interrupt

Specifies response
to a CAN bus-off
interrupt

0 = Hold CAN
chip in reset
1 = Reset CAN
chip and continue

0 = Hold in Reset