Publication 1404-UM001F-EN-P - November 2009
191
Powermonitor 3000 Data Tables Appendix A
Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters
CSP File No.
N/A
Remote I/O BT
N/A
CIP Assy. Inst.
1 (Read), 2 (Write)
No. of Elements
2 (Default)
User Configurable Yes (DeviceNet, EtherNet/IP and ControlNet)
Data Type
Integer (Selectable as Floating Point with DeviceNet, EtherNet/IP and ControlNet)
Data Access
Read/Write
PM3000 Type
All
Remote I/O Discrete Data Provided by Powermonitor (Remote I/O Input Data)
Element
No.
Element name
Range
Comment
1
Relay, KYZ, and alarm bits
-
Bit
Description
00…07
Reserved, used internally for BT information
08
Form C relay state (setpoint output flag 1)
0 = De-energized and not forced
1 = Energized and not forced
09
KYZ output state (setpoint output flag 2)
0 = De-energized and not forced
1 = Energized and not forced
10
Setpoint output flag 3 state
11
Setpoint output flag 4 state
12
Setpoint output flag 5 state
13
Setpoint output flag 6 state
14
Setpoint output flag 7 state
15
Setpoint output flag 8 state
2
Status input bits
Bit
Description
00
Status input 1 state
01
Status input 2 state
02…05
Reserved, returns 0
06
New oscillograph (M6, M8 only)
Indicates at least one capture has been triggered, saved, and is
ready to be read. This bit is cleared when all captures are cleared.
07…11
Reserved, returns 0
12…14
Reserved, used internally for BT information
15
Reserved, returns 0