Metering power results parameters, Metering power results – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 207
Publication 1404-UM001F-EN-P - November 2009
207
Powermonitor 3000 Data Tables Appendix A
Metering Power Results Parameters
CSP File No.
F17
Remote I/O BT
31
CIP Assy. Inst.
16
No. of Elements
13
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Metering Power Results
Element
No.
Modbus
Address
Element name
Units
Range
Comment
0
30301-02
L1 Real Power
Watts (W) 0.0…999.9x10
22
Real power per phase, signed to show
direction.
Refer to Power Results on page 32
.
1
30303-04
L2 Real Power
0.0…999.9x10
22
2
30305-06
L3 Real Power
0.0…999.9x10
22
3
30307-08
Total Real Power
0.0 …999.9x10
22
Total power signed to show direction.
4
30309-10
L1 Reactive Power
Volt-amps
reactive
(VAR)
0.0…999.9x10
22
Reactive power per phase, signed to show
direction.
5
30311-12
L2 Reactive Power
0.0 …999.9x10
22
6
30313-14
L3 Reactive Power
0.0…999.9x10
22
7
30315-16
Total Reactive Power
0.0…999.9x10
22
Total reactive power, signed to show
direction.
8
30317-18
L1 Apparent Power
Volt-amps
(VA)
0.0…999.9x10
22
Apparent power per phase.
9
30319-20
L2 Apparent Power
0.0…999.9x10
22
10
30321-22
L3 Apparent Power
0.0…999.9x10
22
11
30323-24
Total Apparent Power
0.0…999.9x10
22
Total apparent power.
12
30325-26
Metering iteration
-
0…32,767
Increments by 1…32,767, rolls over to 0.