beautypg.com

Event log results parameters, Event log results, Event log results parameters on – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 229

background image

Publication 1404-UM001F-EN-P - November 2009

229

Powermonitor 3000 Data Tables Appendix A

Event Log Results Parameters

CSP File No.

N29

Remote I/O BT

21

CIP Assy. Inst.

34

No. of Elements

14, 17, or 18 (see table)

User Configurable No

Data Type

Integer

Data Access

Read only

PM3000 Type

See table

Event Log Results

Element
No.

Modbus
Address

M4
M5

M
6

M
8

Element Name

Range

Comment

0

30901

• •

Reserved

0

Returns 0

1

30902

• •

Internal identifier

0 …32768

Refer to Reading Data from the Event Log
by Using Communication on page 147

2

30903

• •

Timestamp of event;

Year

Month/day

Hour/minute

Second/hsec

1998…2097

Refer to Expressing Data in Data Tables on
page 82

3

30904

• •

0101…1231

4

30905

• •

0000…2359

5

30906

• •

0000…5999

6

30907

• •

Event type

0…19

Refer to List of Event Types Parameters

7

30908

• •

Event code

-

Refer to Reading Data from the Event Log
by Using Communication on page 147

8

30909

• •

Setpoint type

0…52

9

30910

• •

Setpoint evaluation condition

0…5

10

30911

• •

Setpoint level

integer

exponent

0…9999

11

30912

• •

-21…21

12

30913

• •

Setpoint action/release delay

0…3600 (M4, M5)
0…30,000 (M6, M8)

13

30914

• •

Setpoint action

0…32 (M4, M5)
0…43 (M6, M8)

14

30915

• •

Sustain limit timer

integer

exponent

0…9999

15

30916

• •

-4…21

16

30917

• •

Capture identifier

0…999

17

30918

Reserved

0

Returns 0