Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 164

164
Publication 1404-UM001F-EN-P - November 2009
Chapter 8 Advanced Features
Each data point is expressed in calibrated analog-to-digital (A/D)
converter counts with a resolution of 8192 (13-bit w/sign) or 128 (7-bit
w/sign). A client may calculate the primary-side instantaneous voltage
or current magnitude of each data point by using the following
formula:
Where:
•
M
i
= instantaneous value of the voltage or current data point
•
M
(max rms)
= max rms magnitude
= 399.0 line-to-neutral volts for channels 1, 3, and 5
= 691.1 line-to-line volts for channels 1, 3, and 5
= 10.6 amperes for channels 2, 4, 6, and 7
•
R
max
= maximum resolution
= 8192 for 13-bit w/sign, capture types 0, 1, and 2
= 128 for 7-bit w/sign, capture types 3, 4, and 5
•
N
t
= PT or CT ratio
= PT or CT primary / PT or CT secondary
•
M
data
= value of the data point from the
Configuration/Read-back Data Select
For example, consider the following capture:
•
PT primary = 13.8 kV
•
PT secondary = 120 V
•
CT primary = 100 A
•
CT secondary = 5 A
•
Delta voltage mode (line-to-line)
•
Capture type = 2
You would multiply each data point by the following factor to
correctly display the waveform:
M
i
M
max rms
(
)
2
•
R
max
-------------------------------------- N
t
M
data
•
•
=
Factor
691.1 1.414
•
(
)
8192
⁄
13800
120
⁄
(
)
•
13.72
=
=