Chapter 5 Setpoint Programming and Operation
Example 1 – Simple demand management: To configure setpoint 1 to
energize output relay 1 when projected demand exceeds 100 kW for
more than one second and de-energize relay 1 when projected
demand falls below 90 kW for more than two seconds, you could use
the following settings.
Example 2 – Phase reversal relay: To use setpoint 2 to energize the
output relay as a permissive for starting a three-phase motor, you
could use the following settings.
ATTENTION
These examples are intended to demonstrate setpoint configuration
only. They should not be used as sample application programming
references. Carefully consider all control, operational and safety
issues when designing and implementing setpoint operations.
Simple Demand Management Settings
Parameter
Value
Setpoint number
1
Setpoint type
17 - Projected Watt Demand
Setpoint evaluation condition
0 - Over forward
Setpoint high limit
100,000 watts
Setpoint low limit
90,000 watts
Setpoint action delay
1 second (M4, M5)
10 tenths of a second (M6, M8)
Setpoint release delay
2 seconds (M4, M5)
20 tenths of a second (M6, M8)
Setpoint action type
1 - Energize relay 1 and set alarm flag 1
Phase Reversal Relay Settings
Parameter
Value
Setpoint number
2
Setpoint type
21 - Phase rotation
Setpoint evaluation condition
4 - Equal
Setpoint high limit
1 - ABC
Setpoint low limit
Not used