Technical specifications, Measurement accuracy and range, Ansi/ieee tested – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 337
Publication 1404-UM001F-EN-P - November 2009
337
Technical Specifications Appendix D
The Bulletin 1404 display module is rated as IP65 degree of protection
per International Standard IEC 529. It is rated as Type 4 (Indoor) per
NEMA and UL 508.
Follow the recommended installation guidelines to maintain these
ratings.
ANSI/IEEE Tested
Meets or exceeds the Surge Withstand Capability (SWC) C37.90.1 -
1989 for protective relays and relay systems on all power connection
circuit terminations.
Technical Specifications
The Powermonitor 3000 unit has these specifications.
Measurement Accuracy and Range
See table below for the rating of each parameter
Measurement Accuracy and Range
Parameter
Accuracy in % of Full Scale at +25 °C (77 °F 50/60 Hz Unity Power
Facator
Nominal/Range
M4
M5
M6
M8
Voltage Sense Inputs: V1, V2,
V3
±0.2%
±0.05%
±0.05%
±0.05%
347V/15…399V
L-N
RMS
600V/26…691V
L-L
RMS
Current Sense Input: I1, I2, I3,
I4
±0.2%
±0.05%
±0.05%
±0.05%
5 A/50 mA – 10.6A
RMS
Frequency
±0.05 Hz
±0.05 Hz
±0.05 Hz
±0.05 Hz
50 or 60 Hz/40…75 Hz
Power Functions: kW, kVA,
kVAR
Demand Functions: kW, kVA
Energy Functions: kWH, kVAH
ANSI C12.16 and
EN 61036 Class 1
Accuracy
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
ANSI C12.20 and
EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)
Metering Update Rates
55…80 ms
45…70 ms
45…75 ms
40…90 ms