beautypg.com

Devicenet – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 202

background image

202

Publication 1404-UM001F-EN-P - November 2009

Appendix A Powermonitor 3000 Data Tables

DeviceNet

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

40401

Password

0…9999

0

Valid password required to change configuration data. Returns -1

1

40402

Node address
(MAC ID)

0…64

63

Address 64 enables remote node address programming; there is
no actual node address of 64 defined for the DeviceNet network

2

40403

Baud rate

0…4

0

0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Auto
4 = Programmable

3

40404

Bus Off Interrupt
Action

0…1

0

0 = hold CAN chip in reset
1 = reset CAN chip and continue communication

4

40405

Floating point
data format

0…1

0

0 = Compliant with prior versions, word order swapped
1 = CIP compliant, little Endian

5

40406

Reserved

0

0

Reserved. Must be 0 on a write, returns 0

6

40407

7

40408

8

40409

9

40410

10

40411

11

40412

12

40413

13

40414

14

40415

15

40416

16

40417

17

40418

18

40419

19

40420