Time of use records - real energy and demand, Time of use records – real energy and, Demand – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 263: Time of use records – real energy and demand, Table
Publication 1404-UM001F-EN-P - November 2009
263
Powermonitor 3000 Data Tables Appendix A
Time of Use Records – Real Energy and Demand Parameters
CSP File No.
F56
Remote I/O BT
51
CIP Assy. Inst.
72
No. of Elements
12
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Time of Use Records – Real Energy and Demand
Element
No.
Modbus
Address
Element Name
Range
Units
Comment
0
32401-02
Off-peak real energy
-999,999.0…
999,999.0
MWh
Refer to Reading Time-of-use Log Data on
page 158
1
32403-04
Off-peak real energy
-999.999.999…
999.999.999
kWh
2
32405-06
Off-peak demand
0.0…999.9 x 10
21
Watts
3
32407-08
Mid-peak real energy
-999,999.0…
999,999.0
MWh
4
32409-10
Mid-peak real energy
-999.999.999…
999.999.999
kWh
5
32411-12
Mid-peak demand
0.0…999.9 x 10
21
Watts
6
32413-14
Peak real energy
-999,999.0…
999,999.0
MWh
7
32415-16
Peak real energy
-999.999.999…
999.999.999
kWh
8
32417-18
Peak demand
0.0…999.9 x 10
21
Watts
9
33419-20
Record number
0…12
10
32421-22
Start date
000101…991231
YYMMDD
Start month / day for data stored in this
record, inclusive
11
32423-24
End date
000101…991231
YYMMDD
End month / day for data stored in this
record, inclusive