Appendix A Powermonitor 3000 Data Tables
Basic Device Configuration Parameters
CSP File No.
F10
Remote I/O BT
20
CIP Assy. Inst.
4 (Write), 5 (Read)
No. of Elements
8 (M4, M5), 9 (M6, M8)
User Configurable No
Data Type
Floating point
Data Access
Read / Write
PM3000 Type
See table
Basic Device Configuration
Element
No.
Modbus
Address
Element name
M4
M5
M
6
M
8
Range
Units
Defaul
t
Value
Comment
0
40001-2
Password
•
• •
0…9999
-
0
Valid password required to change
configuration. Returns -1
1
40003-4
Wiring mode
•
• •
0…8
-
6
0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT
5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo
2
40005-6
Potential transformer (PT)
primary
•
• •
1.0…
10,000,000.0
Volts
480.0
The high side of the PT ratio (xxx:xxx)
3
40007-8
PT secondary
•
• •
1.0…600.0
Volts
480.0
The low side of the PT ratio (xxx:xxx)
4
40009-10
I1/I2/I3 current
transformer (CT) Primary
•
• •
1.0…
10,000,000.0
Amps
5.0
The high side of the CT ratio
(xxx:xxx)
5
40011-12
I1/I2/I3 CT secondary
•
• •
1.0…5.0
Amps
5.0
The low side of the CT ratio (xxx:xxx)
6
40013-14
I4 CT primary
•
• •
1.0…
10,000,000.0
Amps
5.0
The high side of the I4 CT ratio
(xxx:xxx)
7
40015-16
I4 CT secondary
•
• •
1.0…5.0
Amps
5.0
The low side of the I4 CT ratio
(xxx:xxx)
8
40017-18
Nominal system voltage
• •
1.0…
10,000,000.0
Volts
480.0
Value is used in the default Sag and
Swell setpoints. (M6 and M8 only)
Nominal line-to-line voltage for Delta
mode and line-to-neutral for Wye and
single-phase modes