Appendix A Powermonitor 3000 Data Tables
Catalog Number and WIN Parameters
CSP File No.
N51
Remote I/O BT
50
CIP Assy. Inst.
64
No. of Elements
29
User Configurable No
Data Type
Integer
Data Access
Read only
PM3000 Type
All
Catalog Number and WIN
Element
No.
Modbus
Address
Element Name
Range
Comment
0
32301
Catalog # text char pair #1
-32,768
…32,767
Catalog number without dashes. Each element contains a character
pair
For each character pair, character 1 = element / 256 and character 2 =
remainder
The 6th character of the catalog string reflects the Current model of the
product
1
32302
Catalog # text char pair #2
2
32303
Catalog # text char pair #3
3
32304
Catalog # text char pair #4
4
32305
Catalog # text char pair #5
5
32306
Catalog # text char pair #6
6
32307
Catalog # text char pair #7
7
32308
Reserved
0
Returns 0
8
32309
9
32310
Hardware series
0…25
Indicates the series of the product; 0 = A, 1 = B
10
32311
WIN text character pair #1
-32,768
…32,767
WIN (warranty identification number). This is the same 10-character
alpha-numeric string printed on the master module label. Each element
contains a character pair
11
32312
WIN text character pair #2
12
32313
WIN text character pair #3
13
32314
WIN text character pair #4
14
32315
WIN text character pair #5
15
32316
Reserved
0
Returns 0
16
32317
17
32318
Original model
0…9
The model as it was originally built. 4 = M4, 5 = M5
18
32319
Current model
Differs from Original model if field-upgraded