Powermonitor 3000 Data Tables Appendix A
Date and Time Parameters
CSP File No.
N11
Remote I/O BT
12
CIP Assy. Inst.
6 (Write), 7 (Read)
No. of Elements
8
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Date and Time
Element
No.
Modbus
Address
Element name
Range
Default
Value
(2)
Comment
0
40101
Password
0…9999
0
Valid password required to change the date and time.
Returns -1
1
40102
Date: year
1998…
2097
1998
1 = January, 2 = February,…12 = December
The internal clock adjusts the date for leap year.
2
40103
Date: month
1…12
1
3
40104
Date: day
1…31
(1)
1
4
40105
Time: hour
0…23
0
0 = 12am, 1 = 1am,…23 = 11pm
The internal clock does not adjust for daylight saving time.
5
40106
Time: minute
0…59
0
6
40107
Time: seconds
0…59
0
7
40108
Time: hundredths of seconds
0…99
0
(1)
On a write, the maximum value for day depends on the values written to month and the year.
(2)
The data and time default values are set if one of the following three conditions occur:
- When the device is first powered-up at the factory.
- A device power-up following the depletion of the real-time clock power source.
- In the event of an abnormal condition which may cause the real-time clock to contain values which are not in the valid range.
The date and time are not set to the default values when Restore Factory Defaults is performed via the display module or communication port.