Configuring setpoints, Setpoint configuration, E setpoint configuration tab – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 128: Not equal setpoint, Setpoint output action logic
![background image](/manuals/578832/128/background.png)
128
Publication 1404-UM001F-EN-P - November 2009
Chapter 5 Setpoint Programming and Operation
Not Equal Setpoint
A not equal setpoint is the opposite of an equal setpoint, activating
when monitored parameter does not equal the Setpoint High Limit for
a time greater than the Setpoint Action Delay. It releases when the
monitored parameter equals the Setpoint High Limit for a period of
time greater than the Setpoint Release Delay.
Setpoint Output Action Logic
When more than one setpoint is configured to control a single
setpoint output action, the following logic applies:
Setpoint output action = Setpoint 1 output action OR
Setpoint 2 output action OR ... Setpoint n output action
Configuring Setpoints
You may configure setpoints by using the display module or by
writing the setpoint configuration table through communication. The
following tables describe setpoint configuration parameters.
Setpoint Configuration
Parameter Name
Parameter Description
Range
Units
Default
Setpoint Number
The number of the setpoint being configured.
1…10 (M4, M5)
1…20 (M6, M8)
-
N/A
Setpoint Type
The parameter value to be evaluated by the
setpoint.
0…52 (Refer to List of
Setpoint Types on
)
-
0
Setpoint Evaluation
Condition
The operator used to evaluate the parameter
value.
0 = Over forward (+)
1 = Over reverse (-)
2 = Under forward (+)
3 = Under reverse (-)
4 = Equal (=)
5 = Not equal (<>)
-
0
Setpoint High Limit
The value being used as a reference to
activate the setpoint for over comparisons, or
to deactivate the setpoint for under
comparisons.
Note: This parameter is non-numeric when
viewed via the display module, and the
Setpoint Type is Phase Rotation or Status
input.
0…10,000,000
Depends on type
0