Network demand sync and time configuration – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 260

260
Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Network Demand Sync and Time Configuration Parameters
CSP File No.
N52
Remote I/O BT
-
CIP Assy. Inst.
65, 66
No. of Elements
20
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
Ethernet
Network Demand Sync and Time Configuration
Element
No.
Modbus
Address
Parameter Name
Range
Default
Value
Description
0
41901
Password
0…9999 0
On a write, the correct password is required to change
configuration data. On a read, -1 is returned.
1
41902
Input mode
0…3
3
Refer to Network Demand / Time Configuration on
page 55
.
2
41903
Broadcast port number
300…
400
300
3
41904
SNTP IP address 1, octet 1
0…255
0
4
41905
SNTP IP address 1, octet 2
5
41906
SNTP IP address 1, octet 3
6
41907
SNTP IP address 1, octet 4
7
41908
Time zone
-12…12
0
8
41909
Time set update interval
0…
32,766
60 s
9
41910
SNTP IP address 2, octet 1
0…255
0
SNTP IP address 2 is a back-up server address when
the first address fails.
10
41911
SNTP IP address 2, octet 2
0
11
41912
SNTP IP address 2, octet 3
0
12
41913
SNTP IP address 2, octet 4
0
13
41914
SNTP IP address 3, octet 1
0
SNTP IP address 3 is a back-up server address when
the secnond address fails.
14
41915
SNTP IP address 3, octet 2
0
15
41916
SNTP IP address 3, octet 3
0
16
41917
SNTP IP address 3, octet 4
0
17
41918
Reserved
0
0
Reserved for future use.
On a write, only a 0 is accepted. On a read, always
returns 0.
18
41919
Reserved
0
0
19
41920
Reserved
0
0