Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 197

Publication 1404-UM001F-EN-P - November 2009
197
Powermonitor 3000 Data Tables Appendix A
14
40215
Restore factory default
config
0…1
-
0
0 = No action 1 = Restore factory default settings
15
40216
Clear status input counters
0…3
-
0
0 = No action
1 = Clear counter #1
2 = Clear counter #2
3 = Clear both
16
40217
Wdog action
0…1
-
1
0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to Watchdog Timeout Action on page 55
17
40218
Force relay output
0…3
-
0
0 = No change
1 = Force energize the relay
2 = Force de-energize the relay
3 = Release force of relay output
Overrides setpoint or pulse output control
18
40219
Force solid-state KYZ output 0…3
-
0
19
40220
Default relay state in event
of communication loss
0…3
-
0
0 = Last state / resume
1 = Last state / freeze
2 = De-energize / resume
3 = De-energize / freeze
Refer to Communication Loss Behavior on
page 140
20
40221
Default KYZ state in event
of communication loss
21
40222
DM text scroll rate
0…1
-
1
0 = Slow; 1 = Fast
22
40223
Energy counter rollover
4…15
Digits 15
Refer to Configurable Energy Counter Rollover
on page 35
23
40224
Forced demand sync delay
0…900
s
10
0 = Disable, 1…900 = number of seconds delay
24
40225
Reserved
0
-
0
Reserved. Must be 0 on a write, returns 0
25
40226
Reserved
0
-
0
Reserved. Must be 0 on a write, returns 0
Advanced Device Configuration
Element
No.
Modbus
Address
Element name
Range
Units Default
Value
Comment