Status error codes, Configuring the event log by using communication – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 146

146
Publication 1404-UM001F-EN-P - November 2009
Chapter 7 Data Logging
Configuring the Event Log by Using Communication
You may configure the Event Log by performing a valid table write to
the
Event Log Configuration/Read-back Record Select
table. This
read/write data table contains these six integer elements:
•
Password: A valid password is required to set configuration
options or -1 to select a record for read-back
•
DeviceNet unique write identifier
•
Read-back mode: see below
•
Status input logging: 0 disables; 1 enables
•
Number of events logged: this read-only element is ignored on a
write
•
Time/date set logging: 0 disables; 1 enables
Status Error Codes
Bits Hex
Description
bit 0
0001h
Master module code flash status
bit 1
0002h
Master module data flash status
bit 2
0004h
Master module RAM Status
bit 3
0008h
Reserved for factory use
bit 4
0010h
Master module NVRAM status
bit 5
0020h
Master module data acquisition status
bit 6
0040h
Master module real time clock status
bit 7
0080h
Reserved for factory use
bit 8
0100h
Reserved for factory use
bit 9
0200h
Display module status
bit 10
0400h
Master module watchdog timer status
bit 11
0800h
Master module optional communication status
bit 12
…
15
1000h
-8000h
Reserved for factory use