Advanced device configuration parameters, Advanced device configuration, Advanced – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 196: Device configuration, Occurs, Refer to advanced device configuration parameters

196
Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Advanced Device Configuration Parameters
CSP File No.
N12
Remote I/O BT
26
CIP Assy. Inst.
8 (Write), 9 (Read)
No. of Elements
25
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Advanced Device Configuration
Element
No.
Modbus
Address
Element name
Range
Units Default
Value
Comment
0
40201
Password
0…9999 -
0
Required to change configuration data.
Returns -1
1
40202
New password
0…9999 -
-1
-1 = no action; 0…9999 = new password;
returns -1
2
40203
Demand period length
-99…
+99
Min
15
Zero or negative demand period length enables
external demand synch.
3
40204
Number of demand periods
1…15
-
1
4
40205
Predicted demand type
0…2
-
0
0 = instantaneous; 1 = 1st order; 2 = 2nd order
5
40206
KYZ control source
0…8
-
7
0 = None (forcing
only)
1 = Wh Forward
2 = Wh Reverse
3 = VARh Forward
4 = VARh Reverse
5 = Vah
6 = Ah
7 = Setpoints
8 = Discrete control (RIO,
DeviceNet)
6
40207
KYZ pulse output scale
1…
30,000
-
10
Refer to Relay and KYZ Output Operations on
page 137
7
40208
KYZ pulse output width
0, 40…
2000
ms
0
0 = KYZ-style transition
40…2000 = pulse duration
8
40209
Relay control source
0…8
-
7
Same choices as KYZ control source
9
40210
Relay pulse output scale
1…
30,000
-
10
Refer to Relay and KYZ Output Operations on
page 137
10
40211
Relay pulse output width
0,
40…
2000
ms
100
0 = KYZ-style transition
40…2000 = pulse duration
11
40212
RMS resolution
0…1
-
0 (M4)
1 (M5, 6 or 8)
0 = Nominal
1 = High
12
40213
RMS result averaging
0…1
-
0 (M4)
1 (M5, 6 or 8)
0 = No averaging.
1 = Average of the last 8 results
13
40214
Frequency averaging
0…1
-
1
0 = none; 1 = last 8 cycles