Advanced Features Chapter 8
•
Capture clear status: Read-only bitfield that indicates which
capture numbers are clear. Bit 0 (LSB) corresponds to capture 1,
bit 1 to capture 2 and so on. For each bit, 1 indicates clear, 0
indicates not clear.
•
Capture ready status: read-only bitfield that indicates which
capture numbers contain captures that are ready to read. Same
bit correspondence as above. For each bit, 1 indicates the
capture is ready, 0 indicates no capture or not yet ready. If a
client reads a capture that is not ready, -1 is returned for all data
points.
Block Number
The block number and the total number of data reads required to read
an entire capture depend on the communication option and the
capture type.
See the
The block number range is 1 to the number of Data reads required
listed in the table.
Capture Type
The properties associated with the capture type options are listed in
the
table.
You may select a capture type that best suits your application
requirements. A higher sample rate provides a more accurate
representation of the waveform when higher-order harmonics and
transients are present. Higher data resolution provides more accuracy
of each data point. Capture type 5 combines low sampling rate and
low resolution, but captures almost 7 seconds of waveform at 60 Hz.
Capture Type Properties
Capture
Type
Sampling
Rate
Data
Resolution
Samples per
Cycle at 60 / 50
Hz
Total Cycles per
Channel at 60 / 50
Hz
Capture
Duration
(seconds)
Data Reads Required
DeviceNet
Other Comms
0
5.4 kHz
13-bit
w/sign
90 / 108
51.1 / 42.6
0.85
230
92
1
2.7 kHz
45 / 54
102.2 / 85.2
1.70
2
1.35 kHz
22.5 / 27
204.4 / 170.3
3.40
3
5.4 kHz
7-bit
w/sign
90 / 108
102.2 / 85.2
1.70
460
184
4
2.7 kHz
45 / 54
204.4 / 170.3
3.40
5
1.35 kHz
22.5 / 27
408.8 / 340.7
6.81