Chapter 3 Powermonitor 3000 Unit Operations
Refer to the Device Configurations Summary table on
for a
summary of basic and advanced device configuration settings. You
may use a copy of this table to record your configuration settings.
Basic Device Configuration
The basic unit configuration sets the wiring mode, PT ratios and CT
ratios to match your power system. Every power monitor requires
basic configuration. To perform basic configuration by using the
display module, navigate through these menus: PROG. > PASS? >
CONFIGURATION > BASIC. You may also set the basic device
configuration via communication by writing to the
table.
Wiring Mode
Select the wiring mode to match the physical configuration of your
power system.
Your wiring mode choice must match the wiring diagrams found in
the Powermonitor 3000 Unit Installation Instructions, publication
1404-IN007, for proper operation and accuracy.
Your choices include the following:
•
Delta 3 CT
•
Delta 2 CT
•
Direct Delta 3 CT
•
Direct Delta 2 CT
•
Open Delta 3 CT
•
Open Delta 2 CT
•
Wye (default)
•
Single Phase
•
Demo
You may choose Demo mode for training or demonstration purposes.
In Demo mode, the power monitor returns internally generated
results.