Powermonitor 3000 Data Tables Appendix A
Controller Command Parameters
CSP File No.
N53
Remote I/O BT
-
CIP Assy. Inst.
67
No. of Elements
1
User Configurable No
Data Type
Integer
Data Access
Write only
PM3000 Type
Ethernet
Controller Command
Element
No.
Element Name
Range
Default
Value
Comment
0
Controller Command
Bits 0
0…32,767
0
Refer to Network Demand / Time
Configuration on page 55
Daylight Saving Time Configuration Parameters
CSP File No.
N54
Remote I/O BT
47
CIP Assy. Inst.
68 (Write), 69 (Read)
No. of Elements
10
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Daylight Saving Time Configuration
Element
No.
Modbus
Address
Element name
Range
Default
Comment
0
42101
Password
-1…9999
0
Required for configuration. Returns -1
1
42102
DST Enable
0…1
0
0 = Disabled, 1 = Enabled
2
42103
DST Start Month
1…12
3
1 = January, 2 = February…
3
42104
DST Start Day
0…6
0
0 = Sunday, 1 = Monday…
4
42105
DST Start Day Instance
1…5
2
1 = 1st, 2 = 2nd, ... 5 = Last
5
42106
DST Start Hour
0…23
2
0 = 12:00 midnight, 1 = 1:00 AM…
6
42107
DST End Month
1…12
11
1 = January, 2 = February…
7
42108
DST End Day
0…6
0
0 = Sunday, 1 = Monday…
8
42109
DST End Day Instance
1…5
1
1 = 1st, 2 = 2nd, ... 5 = Last
9
43110
DST End Hour
0…23
2
0 = 12:00 midnight, 1 = 1:00 AM…