Energy and demand results, Display module functionality – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 38
38
Publication 1404-UM001F-EN-P - November 2009
Chapter 3 Powermonitor 3000 Unit Operations
Display Module
Functionality
The display module is a simple terminal that allows you to easily view
metering parameters or change configuration items. The display
module uses three modes of operation.
•
Display mode allows you to view power monitor parameters
including metering, setpoint, min/max log, event log and
self-test information. You may also select a default screen to be
displayed at power-up or after 30 minutes without key activity.
•
Program mode allows you to change configuration parameters,
with security against unauthorized configuration changes. Each
power monitor is password protected. In Program mode, the
display module phase indicators (L1,L2,L3,N) flash.
•
Edit mode allows you to modify the selected parameters. In Edit
mode, the parameter being modified flashes, and the phase
indicators (L1,L2,L3,N) remain solid.
Energy and Demand Results
Parameter Description
Range
Units
Kilo-Watt Hours Forward
The total real power consumed
0…1.0x10
12
kWh
Kilo-Watt Hours Reverse
The total real power produced
Kilo-Watt Hours Net
The sum of forward and reverse power
Kilo-VAR Hours Forward
The total reactive power consumed
0…1.0x10
12
kVARh
Kilo-VAR Hours Reverse
The total reactive power produced
Kilo-VAR Hours Net
The sum of forward and reverse reactive power
Kilo-VA Hours Net
The total apparent power consumed
0…1.0x10
12
kVAh
Amp Hours Net
Accumulated amp-hours consumed
0…1.0x10
12
Ah
Demand Current
The calculated demand for average current
0…999.9x10
21
Amps
Max Demand Current
The maximum (peak) demand for current. (included in
Min/Max Log)
Demand Kilo-Watts
The calculated demand for real power
0…999.9x10
21
kW
Max Demand Kilo-Watts
The maximum (peak) demand for real power
(included in Min/Max Log)
Demand Kilo-VARs
The calculated demand for reactive power
0…999.9x10
21
kVAR
Max Demand Kilo-VARs
The maximum (peak) demand for reactive power
(included in Min/Max Log)
Demand Kilo-VA
The calculated demand for apparent power
0…999.9x10
21
kVA
Max Demand Kilo-VA
The maximum (peak) demand for apparent power
(included in Min/Max Log)
Projected Current Demand
(1)
The projected demand for average current
0…999.9x10
21
Amps
Projected Kilo-Watt Demand
(1)
The projected demand for real power
0…999.9x10
21
kW
Projected Kilo-VAR Demand
(1)
The projected demand for reactive power
0…999.9x10
21
kVARs
Projected Kilo-VA Demand
(1)
The projected demand for apparent power
0…999.9x10
21
kVA
(1)
Values returned depend on user selection of projected demand type in Advanced Configuration.