Transient analysis configuration – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 180

180
Publication 1404-UM001F-EN-P - November 2009
Chapter 8 Advanced Features
Transient Capture
Transient Analysis Configuration
Perform a table write to the
Configuration/Read-back Select
to configure transient analysis. This
read/write table of 13 floating-point elements contains the following
configuration, command and read-back select parameters:
•
Password: required for configuration and command. Use a valid
password or -1 for read-back select. Range 0000…9999,
default 0, returns -1
•
DeviceNet unique write identifier: range -32,768…32,767,
default 0
•
Capture number: selects a capture for read-back. Range 0…6,
default 1
•
Cycle number: selects a cycle for read-back. Range 1…12,
default 1
•
Read-back mode: 0 = Auto-increment mode; cycle number
increments after each read of the
table. 1 = Manual-increment mode; only mode supported
by DeviceNet and Ethernet communication. Default 0
•
Detection mode: selects channels to monitor. 0 disables transient
detection, 1 = voltage channels only, 2 = current channels.
Default 1
•
Auto-threshold set command: 0 = do nothing, 1 = set threshold.
Default 0
•
Auto-threshold set duration: range: 1…3600 seconds, default 10