Rs-232 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 203
Publication 1404-UM001F-EN-P - November 2009
203
Powermonitor 3000 Data Tables Appendix A
RS-232
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
40401
Password
0…9999
0
Required to change configuration data. Returns -1
1
40402
Hardware port
0…1
0
Select active port
0 = RS-232 port
1 = Native RS-485 port
2
40403
Protocol
0…3
0
Communication protocol for the native
communication port.
0 = DF1 half-duplex slave
1 = Modbus RTU slave
2 = Auto Sense - Selects the protocol based on the
incoming communication packets
3 = DF1 full-duplex
3
40404
Delay
0…15
2 (10 ms)
Specifies the delay before responding to an
external request., useful with slow external
devices (such as RF modems)
4
40405
Baud rate
0… 6
3
0 = 1.2 Kbps
1 = 2.4 Kbps
2 = 4.8 Kbps
3 = 9.6 Kbps
4 = 19.2 Kbps
5 = 38.4 Kbps
6 = 57.6 Kbps
5
40406
RS-232 address
1…247
(1)
Identifies the device on the link. 0 is typically used
by the DF1 master. 255 is the broadcast address
6
40407
Data format
0…2
0
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Even parity, 8 data bits, 1 stop bit
2 = Odd parity, 8 data bits, 1 stop bit
7
40408
Flow Control (Handshaking)
0…1
0
Data flow control for RS-232/RS-485 port.
0 = None
1 = Hardware RTS/CTS
8
40409
RTS On Delay
0…9995
ms
0
9
40410
10
40411
Inter-character timeout
Specifies the minimum delay between characters
that indicates the end of a message packet. 0 = 3.5
character times.
11
40412
Error checking
0…1
0
0 = CRC
1 = BCC