beautypg.com

Load factor log configuration/read-back select, Ite to the – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 247

background image

Publication 1404-UM001F-EN-P - November 2009

247

Powermonitor 3000 Data Tables Appendix A

Load Factor Log Configuration/Read-back Select Parameters

CSP File No.

N41

Remote I/O BT

16

CIP Assy. Inst.

49 (Write), 50 (Read)

No. of Elements

6

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

M6, M8 only

Applies to:

Load Factor Log Results Parameters on

page 248

Load Factor Log Configuration/Read-back Select

Element
No.

Modbus
Address

Element Name

Range

Default
Value

Comment

0

-

Password

0…9999

0

Required for configuration or command,
-1 for readback select, returns -1

1

-

Record to read-back

0…12

0

Refer to Reading the Load Factor Log on
page 178

2

-

Read-back mode

0…1

1

3

-

Clear peak / reset average command

0…1

0

4

-

Auto clear/reset day

0…31

31

5

-

Reserved

0

0