beautypg.com

Figure 3.4, In step 4, Figure 3.4 for – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 55

background image

Publication 1394-5.0 — May 2000

Wiring System, Axis, and Shunt Modules, and Motors (for all systems)

3-9

4. Close the system module door.

5. Go to Grounding Your 1394 System.

Figure 3.4
Ground Jumper Locations for the 5 and 10 kW System Modules

Setting the Ground Jumper in a 22 kW System Module for
Ungrounded Power Configurations

This procedure assumes that you have bonded and mounted your
1394x-SJT22-x system module to the subpanel and that there is no
power applied to the system. To set the ground jumper:

Important: If you have grounded power distribution, you do not

need to set the ground jumper. Go to Grounding Your
1394 System.

1. Verify that all 24V control and 360/480V power has been

removed from the system.

2. Open the system module door.

3. Disconnect both ends of the input wiring board ribbon cable.

Refer to Figure 3.5 for the location of the ribbon cable.

4. Remove the upper and lower input wiring board screws. Refer to

Figure 3.5 for the location of the screws.

5. Remove the input wiring board.

1394C-SJT

xx-x

(5 and 10 kW Series C)

Upper
Control Board
Screw

J4

J5

J6

Ribbon
Cable
Connector

Side

Control Board

Screw

Lower
Control Board
Screw

J27

J26

GND3

1394-SJT

xx-x

(5 and 10 kW Series A and B)

This manual is related to the following products: