Publication 1394-5.0 — May 2000

8-12

Configuring Your 1394 Analog Servo System

[Feed Fwd Gain]

Controls the negative feedforward gain of the
velocity command contribution to the velocity
regulator torque loop. Setting this to a value
greater than zero reduces the velocity feedback
overshoot in response to a step change in the
velocity reference. The velocity loop response to
a load disturbance is unaffected by the Feed
Forward Gain. The default value will be
satisfactory in most cases.

Parameter Numbers

376, 377, 378, 379

Parameter Group

Vel Loop Data

Display Units

None

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

0% of [Vel Command]

Maximum Value

100% of [Vel Command]

Default Value

0

[Hardware Version]

This parameter specifies the revision level of the
system module hardware.

Parameter Numbers

25

Parameter Group

Monitor Parms

Display Units

None

Parameter Type

Read Only

Linkable

No

[I(t) Cur Lim]

This parameter displays the present level of the
I(t) current limit for this axis.

Parameter Numbers

344, 345, 346, 347

Parameter Group

Linear List

Display Units

amps

Parameter Type

Read Only

Linkable

No

[Id Cur Ref]

This parameter displays the present level of the
Id current reference for this axis.

Parameter Numbers

236, 237, 238, 239

Parameter Group

Torq Data

Display Units

amps

Parameter Type

Read Only

Linkable

No

[Id RPM End]

This parameter determines the velocity at which
maximum Id current will be applied. It is
automatically changed when a motor is selected
by [Motor Type].

Note: Before making modifications to Mtr Data
parameters, [Motor Type] must be set to "custom
motor".

Parameter Numbers

176, 177, 178, 179

Parameter Group

Mtr Data

Display Units

rpm

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

0.0 rpm

Maximum Value

8000.0 rpm

Default Value

This is determined by the motor catalog number.

[Id RPM Start]

This parameter determines the velocity at which
Id current will start to be applied. It is
automatically changed when a motor is selected
be [Motor Type].

Note: Before making modifications to Mtr Data
parameters, [Motor Type] must be set to "custom
motor".

Parameter Numbers

172, 173, 174, 175

Parameter Group

Mtr Data

Display Units

rpm

Parameter Type

Read/Write

Change While Running

Yes

Linkable

No

Minimum Value

0.0 rpm

Maximum Value

5600.0 rpm

Default Value

This is determined by the motor catalog number.