Grounding for 1394 ce requirements, Filter – Rockwell Automation 1326 Digital AC Multi-Axis Motion Control System User Manual User Manual

Page 262

background image

Publication 1394-5.0 — May 2000

B-30

Interconnect and CE Diagrams

Grounding for 1394 CE Requirements

Refer to the figure below for CE grounding requirements for 1394
installation.

Figure B.25
1394 CE Requirements

User-Supplied

Discrete I/O

User-Supplied

24V

Power Source

Three-Phase

Contactor

Bonded System

Ground Bar

Enclosure

1

2

Enclosure

Resolver/

High Resolution

Feedback

Cables

Conduit Clamp

Ground Conduit to Enclosure

Filtered Conductors

Unfiltered Conductors

Three-Phase

Mains with

Ground

360 Shield
Termination at
Enclosure by
User

JOG

ESC

SEL

E

3

Filter

4

5

6

The GMC version requires an Allen-Bradley filter (catalog number SP-74102-006-01, -02, -03) or equivalent Roxburgh filter (catalog number MIF323-GS, or
MIF330-GS, or MIF375-GS respectively).
Mount the filter as close to the 1394 as possible. Isolate filtered conductors from unfiltered conductors. It is recommended to mount the filter to the right of the
axis modules to simplify routing of filtered (clean) and unfiltered (noisy) wiring. The load end of the filter is considered noisy and should be routed carefully
away from clean signal wires.

1

2

360 shield termination for system module cables at the enclosure is required only for the GMC version. The termination for axis module cables are required

for all versions of the 1394. Use Wieland Electric commercial clamps or equivalent.

3

The filter shown is sized for one 1394. Equivalent filters may be used for multiple units. Size the filter following the manufacturers recommendation.

4

The 1326-

xxxx-Ex

-xxx bulkhead cables are designed specifically to provide

shield termination.

5

Wire 5 and 10 kW (Series C) optional three-phase input power to the system via connector J10-4.

6

Ground bar is customer-supplied item for all Series A and B systems. Ground bar is included on all Series C systems.

Important: All three-phase power in the cabinet must be filtered to reduce EMI.

360