99

6 Configuration

Adjusted state: The actual value has left the alarm range and reached the new setpoint value.
The output signal remains inactive until the actual value returns to the alarm range.

Status after change of configuration

Modified parameters are incorporated immediately. If a switch-on delay was active before or
during the configuration change, the delay time starts over.

Behavior after power on

The output signal status is not saved. Limit value monitoring starts after initialization according
to its configuration.

6.11.1

Alarm

In addition to evaluation of the limit value monitoring output signal, there is also the option to
make an entry in the event list in the case of an alarm or to form a collective alarm.

Setup dialog

Parameters

w2 = x

(1)

1

0

Parameter

Selection/settings

Description

Alarm type

The alarm type is not set by default.

Collective alarm

Alarm results in collective alarm of con-
troller module.

Event

Alarm results in an entry (event text) in
the event list.

Alarm active at

High (1)

Alarm at high level (1)

Low (0)

Alarm at low level (0)

Event text

Use default text or select other text from
the list.

Text that is entered in the event list for
an alarm (if Alarm type = "Event").

?