7 Parameterization

7.1

Controller parameters

Two parameter blocks can be defined for each of the four controller channels. Changeover of
parameter blocks is performed separately for each controller channel by a digital signal.

Setup dialog

Parameters

The following table shows the parameters in one parameter block. The same parameters are
also available for the second parameter block.
Depending on the configured controller type, certain parameters are omitted or have no effect.
Parameters that appear in pairs such as Proportional band 1 and 2 refer to the first and second
controller outputs.

TIP!
The parameters described in this section can be entered either with the setup program or on
the multifunction panel.

Parameter

Setting

Description

Proportional band
1

(Xp1)

0 to 9999

Value for the proportional band

The controller structure has no effect if
Xp = 0 (behavior identical to limit value
monitoring)!

For a continuous controller, Xp must be

 0.

Proportional band
2

(Xp2)

0 to 9999

Derivative time 1

(Tv1)

0 to 80 to 9999 s

The derivative time influences the differ-
ential component (D component) of the
controller output signal.

The greater the derivative time, the
more effect the D component has.

Derivative time 2

(Tv2)

0 to 80 to 9999 s