7 parameterization, 1 controller parameters, Parameterization – JUMO 705010 mTRON T - Multichannel Controller Module Operating Manual User Manual
Page 117: Controller parameters
117
7 Parameterization
7.1
Controller parameters
Two parameter blocks can be defined for each of the four controller channels. Changeover of
parameter blocks is performed separately for each controller channel by a digital signal.
Setup dialog
Parameters
The following table shows the parameters in one parameter block. The same parameters are
also available for the second parameter block.
Depending on the configured controller type, certain parameters are omitted or have no effect.
Parameters that appear in pairs such as Proportional band 1 and 2 refer to the first and second
controller outputs.
TIP!
The parameters described in this section can be entered either with the setup program or on
the multifunction panel.
Parameter
Setting
Description
Proportional band
1
(Xp1)
0 to 9999
Value for the proportional band
The controller structure has no effect if
Xp = 0 (behavior identical to limit value
monitoring)!
For a continuous controller, Xp must be
0.
Proportional band
2
(Xp2)
0 to 9999
Derivative time 1
(Tv1)
0 to 80 to 9999 s
The derivative time influences the differ-
ential component (D component) of the
controller output signal.
The greater the derivative time, the
more effect the D component has.
Derivative time 2
(Tv2)
0 to 80 to 9999 s