7 Parameterization

Transmission behavior

The transmission behavior (controller structure) is determined by the configuration of the pa-
rameters for the proportion band (P component), derivative time (D component), and reset time
(I component).

7.2

Controller types

Two-state controller

This controller has a switched output and can be parameterized with P, PI, PD, or PID trans-
mission behavior. The proportional band Xp must be greater than 0 for the controller structure
to take effect.
If Xp = 0 the behavior corresponds to the function of limit value monitoring with switching dif-
ferential Xd1 (working point Y0 = 0 %):

Influence of working point Y0 on the switching behavior

Xd1

0 %

100 %

y

w

x

Xd1

0 %

100 %

y

w

x

w-Xd1

Y0 = 0 %

Xd1

0 %

100 %

y

w

x

w+Xd1

Y0 = 100 %

Xd1

0 %

100 %

y

w

x

w-Xd1

Y0 = -100 %

Xd1

w-2*Xd1