8 Configuration – in setup program only

126

8.2

Math/Logic

The optional Math/Logic function can be used for four formulae, which can be used freely either
for mathematical calculations (analog values) or for logical links (binary values).
Fixed formulae for calculating the differential, ratio, and relative humidity are also provided. In
this case, two analog values (variable A and B), e.g. the measured value of analog input 1 and
2 are linked to each other. The dry-bulb temperature and the wet-bulb temperature are required
for calculating the relative humidity and should be determined with a psychrometric humidity
sensor.
The results are available in the analog selector or digital selector. If the function is not active,
the math value = 3.0E+37 and the logic value = 0 (FALSE).

Setup dialog

Parameters

Parameter

Selection/settings

Description

Math function

Without function

Function is switched off.

Mathematics

Mathematical links with freely selectable
variables and operators

Logic

Logical links with freely selectable vari-
ables and operators

Difference

Difference between the measured value
and analog signal A and B (A - B)

Ratio

Ratio between the measured value and
analog signal A and B (A / B)

Humidity

Calculation of relative humidity

Analog signal A: dry-bulb temperature
Analog signal B: wet-bulb temperature

Unit

6 characters (%)

Unit in which the math result (analog
value) is displayed.

Variable A

Analog selector

Analog signal A (for calculating differen-
tial, ratio, and humidity)

?