6 Configuration

Setpoint

If you are only using an analog signal for setpoint input, select it directly from the analog se-
lector, for example "NV_C01Setpoint". It is then not possible to specify a fixed setpoint value
or a correction value. The ramp function is not available in this case either.
If you require a fixed setpoint value, select the setpoint value for the relevant controller chan-
nel here, for example "SP01Setpoint1". You can then enter the setpoint value in the setpoint
value configuration (setpoint value function) or on the controller screen of the multifunction pan-
el.
If you are using an analog signal in conjunction with a correction value as a setpoint
value
, select the active setpoint value of the setpoint value function, for example "SP01Active".
You can then enter the correction value in the setpoint value configuration (setpoint value func-
tion) or on the controller screen of the multifunction panel. During this, the current value of the
analog signal (external setpoint value), the correction value (setpoint value), and the active set-
point value (external setpoint value + setpoint value) are displayed on the controller screen.
To use the ramp function, select the current setpoint value of the ramp function, for example
"SP01RampOutput". Here, the ramp end value corresponds to the active setpoint value (exter-
nal setpoint value + setpoint value). Enter the setpoint value as the ramp end value in the set-
point value configuration or on the controller screen (multifunction panel).
Chapter 6.10 "Setpoint values", page 90

Decimal place y

R

Decimal places of output level feedback (y

R

)

(Selection options as for Decimal place
x)

Param. set
switching

Digital selector (Inactive)

Signal (high-active) for changeover from
parameter block 1 to parameter block 2

Turn-off
controller

Digital selector (Inactive)

Signal (high-active) for switching off the
controller

If "Inactive" is selected, the controller is
always switched on.

Parameter

Selection/settings

Description