6 Configuration

Performing fine adjustment

1) Determine the lower value (as low and constant as possible) with the reference measuring

device.
Example: Set furnace temperature to 20 °C.

2) Enter the display value as the actual start value and the reference value as the target start

value.
Example: Enter 15 and 20.

3) Determine the upper value (as high and constant as possible) with the reference measuring

device.
Example: Increase furnace temperature to 80 °C.

4) Enter the display value as the actual end value and the reference value as the target end

value.
Example: Enter 70 and 80.

Characteristic line

The following diagram shows the changes in the characteristic line caused by the fine adjust-
ment (point of intersection with the x axis as well as the gradient).

Resetting the fine adjustment

The following settings must be made to reverse the fine adjustment:
Actual start value = target start value
Actual end value = target end value