6 Configuration

Description of the function

Monitoring starts as soon as the maximum output level is produced in heating mode (see ex-
ample) or as soon as the minimum output level is produced in cooling mode. Starting from this
point, the actual value must leave the monitoring band – the range around the actual value at
the start of monitoring – within the response time. If it does not, an alarm is triggered.
On leaving the monitoring band, the actual value at the time is used as a reference value for a
new monitoring band. The response time starts over.
Monitoring ends as soon as the maximum or minimum output level is no longer produced.

y

M

t

y

x

t

T

R

Dx

x

y

t1

t2

x Actual value

x Monitoring band

y Output level

y

M

Max. output level (e.g. 100 %)

t1 Start of monitoring

T

R

Response time

t2 End of monitoring